NOTE:This Installation Guide describes GP4000 Series except GP-4100 Series, GP-4201TM and GP-4301TM.OverviewPackage Contents...
12 EnglishPart Numbers and Functions5. GP-4600 SeriesA: Status LED (see page.13)B: Power Input Terminal Block (AC model), Power Plug Connector (DC
13Part Numbers and Functions English6. LED Indications(1) Status LED(2) SD Card access LED(3) Ethernet LEDColor Indicator DescriptionGreen ON Offlin
14 EnglishInterfaceSerial InterfaceNote: For instructions on how to connect to other devices, always refer to the “GP-Pro EX Device/PLC Connection
15Interface English1. Connection for Serial InterfacePin assign of each serial interface is explained in reference page.COM1 COM2GP-4201T RS-232C or
16 EnglishInterface2. RS-232CD-Sub 9 pin plug connector via an RS-232C cable.Note: (1) You can switch pin #9 between RI and VCC via software. To p
17Interface English3. RS-422/485D-Sub 9 pin plug connector via an RS-422/485 cable.Interfit bracket is #4-40 (UNC).Recommendations:• Cable Connector
18 EnglishInterface4. RS-485 (isolation)D-Sub 9 pin socket connector via an RS-485/PROFIBUS/MPI cable. Note: (1) You can supply power to the Siemen
19 EnglishInstallation1. Installation Requirements•Decide on the thickness of the enclosure wall, based on the level of strength required: 1.6 mm (0
20 EnglishInstallation• When installing the GP unit in a slanted position with an incline more than 30°, the ambient temperature must not exceed 40
21Installation English3 Create a Panel Cut and insert the GP into the panel from the front. ACRBGP-4200 Series GP-4300 Series GP-4400 SeriesGP-450
4 EnglishOverviewPackage ContentsThe following items are included in the package. Before using the GP unit, please confirm that all items listed her
22 EnglishInstallation4 Insert the installation fasteners into the GP unit’s insertion slots on the top and bottom sides. (left and right sides for
23Installation English NOTICEBROKEN ENCLOSURE• Do not exert more than 0.5 Nm (4.4 in-lb) of torque when tightening the fastener’s screws.• For use o
24 EnglishInstallation3. Removal ProceduresStep Action1 Loosen the installation fasteners (4) from the GP unit.2 Remove the GP unit slowly from the
25 EnglishWiringWiringNote: • The shield ground (SG) and FG terminals are connected internally in the GP unit.• When the functional ground (FG) te
26 EnglishWiring1. Connecting the AC Power CordUse copper conductors only.The temperature rating of field installed conductors: 75C° (167°F) only.*1
27Wiring English2. Connecting the DC Power CordUse copper conductors only.The temperature rating of field installed conductors: 75°C (167 °F) only.*
28 EnglishWiringPower Connector SpecificationsNote: The DC power supply connector (plug) for GP-4200/4300/4400 Series is PFXZCBCNDC1 (manufactured
29Wiring EnglishHow to connect the DC Power CordNote: • Do not solder the wire directly to the power receptacle pin.• To prevent the possibility o
30 EnglishWiring3. Wiring CautionsImproving Noise/Surge Resistance• The GP unit’s power supply cord should not be bundled with or kept close to main
31 EnglishUSB Cable ClampUSB Cable ClampWhen using a USB device, attach a USB cable clamp to the USB interface to prevent the USB cable from being d
5Overview EnglishAbout the ManualThis manual describes wiring and installation procedures. For more detailed information, refer to the manuals indic
32 EnglishUSB Cable Clamp2. Removing the USB Cable3 As shown, pass the tie through the clip hole. Next, turn the tie and pass it through the head so
33 EnglishStandardsRelevant StandardsThe GP unit is manufactured in accordance with:• Standard UL 508 and CSA C22.2 n°142 for Industrial Control Equ
34 EnglishStandardsWARNINGRISK OF EXPLOSION IN HAZARDOUS LOCATIONS• Do not connect or disconnect equipment unless power has been switched off or the
35Standards EnglishThe GP unit must be installed, used and maintained in accordance with:• Standard WEEE, Directive 2002/96/EC• Standard RoHS, Direc
36 English
6 EnglishElectrical Specifications1. GP-4200/4300/4400 SeriesSpecificationGP-4200 Series GP-4300 Series GP-4400 SeriesPower SupplyRated Input Voltag
7Electrical Specifications English2. GP-4500/4600 SeriesSpecification GP-4500/4600 SeriesDC Model AC ModelPower SupplyRated Input Voltage 24 Vdc 100
8 EnglishPart Numbers and Functions1. GP-4200 Series A: Status LED (see page.13)B: USB (mini-B) InterfaceC: USB (Type A) InterfaceD: Serial Interfa
9Part Numbers and Functions English2. GP-4300 Series A: Status LED (see page. 13)B: USB (Type A) Interface C: Serial Interface (COM1)D: Serial Inte
10 EnglishPart Numbers and Functions3. GP-4400 SeriesA: Status LED (see page.13)B: USB (Type A) InterfaceC: Serial Interface (COM1)D: Serial Interf
11Part Numbers and Functions English4. GP-4500 SeriesA: Status LED (see page.13)B: Power Input Terminal Block (AC model), Power Plug Connector (DC