6
COM2
Always connect close to the GP unit's COM port when terminating with the termina-
tion pins (TRMRX/TRMTX).
Recommended Cable
Connector
XM2A-0901 <made by OMRON Corp.>
XM2D-0901 <made by OMRON Corp.> (AGP-3302B only)
Recommended Jack Screw XM2Z-0073 <made by OMRON Corp.>
Recommended Cable Cover XM2S-0913 <made by OMRON Corp.>
Fitting fastener #4-40 (UNC)
Pin #
RS422/RS485 (Except AGP-3302B) RS422 (AGP-3302B only)
Signal Name Meaning Signal Name Meaning
1 TRMRX
Termination
(Receiver side: 100 )
RDA Receive Data A(+)
2 RDA Receive Data A(+) RDB Receive Data B(-)
3 SDA Send Data A(+) SDA Send Data A(+)
4 RS(RTS) Request for Send ERA Data Terminal Ready A(+)
5 SG Signal Ground SG Signal Ground
6VCC
+5 V ±5 % Output 0.25 A
*1
*1 The VCC output for Pin #6 is not protected against overcurrent. To prevent damage or unit
malfunctions, use only the rated current.
CSB Clear to Send B(-)
7 RDB Receive Data B(-) SDB Send Data B(-)
8 SDB Send Data B(-) CSA Clear to Send A(+)
9TRMTX
Termination
(Receiver side: 100 )
ERB Data Terminal Ready B(-)
Shell FG
Frame Ground
(Common with SG)
FG
Frame Ground
(Common with SG)